D770-25-00 2 I56-1427-001R
Locate it where vibration, shock, and mechanical loading
are minimal. Refer to piping diagram (Figure 2 on page 2).
a. Mount the device directly to the line via the 1/2" NPT
pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.
b. Apply tightening torque to the brass hex portion of
device.
High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.
3. Wire the device in accordance with the National
Electrical Code. Two 1/2” NPT conduit entry holes have
been provided in the mounting base to accept explosion
proof conduit fittings. If necessary, remove conduit entry
plug with 3/8” square wrench.
4. Connect wiring to terminals (see Figure 3 and Table 1).
Adjustments To Factory Settings
Figure 2. Typical piping diagram for EPS10EXP
A78-2398-00
Figure 3. Switch terminals:
Table 1. Electrical connections (referenced at facto-
ry settings):
COMMON
TERMINALS
TERMINAL
“A”
SWITCH #2
TERMINAL
“B”
GROUND
SCREW
(GREEN)
SWITCH #1
A78-2346-02