System-sensor FAAST Networking Manual do Utilizador Página 35

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 34
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Networking
35
Field Description
Email The e-mail address of the recipient to receive notification
Alert
E-mail generated when the device has reached the specified alarm level
Action 1
Action 2
Fire 1
Fire 2
Minor E-mail generated when the device detects a Minor Fault
Urgent E-mail generated when the device detects an Urgent Fault
Isolate E-mail generated when the device has been placed into Isolate Mode
10. When the desired e-mail settings have been entered, click the Save
icon
11. The following message will appear
If all settings are correct, select Ye s to send the new configuration to the detector. If you would like to make changes, select No.
Note: To send the configuration to the detector manually, right-click on the device and select Send Conguration.
12. After receiving the configuration, the detector will shut down and restart. The detector will then begin operating using the
new e-mail settings.
Note: The e-mail client requires 5 minutes from power-on to initialize. No e-mails will be sent during this period.
Vista de página 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40

Comentários a estes Manuais

Sem comentários