F440-02-00 1 I56-648-03
RTC Remote Test Coil Kit for use
with the B404B and B404BT Bases
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The System Sensor Model RTC Remote Test Coil Kit allows
for the remote testing of duct detectors using the B404B or
B404BT bases that are installed in inconvenient or difficult-
to-reach locations. Model RTC can be installed in almost
any convenient location and can be attached to a standard
2" X 4" electrical box.
The National Fire Protection Association has published
standards and practices for the installation and use of this
device. As a result, System Sensor recommends that the in-
staller be familiar with these standards and practices, local
codes, and any special requirements of the authority hav-
ing jurisdiction.
RTC Contents
1 RTS451 Remote Test Station
2 #8 x 1/4" pan head screws for mounting bracket
1 Test Coil/Replacement Ring
1 Screw Pack (2 mounting Assembly screws)
1 Jumper with spade lugs
1 M02-04 Test Magnet
Installation
Installation of the Model RTC consists of attaching the test
station to the mounting surface, mounting the test coil on
the detector, and routing the necessary wiring between
them. This installation procedure assumes that the
associated detector base is already installed and ready for
operation.
Figure 1:
A78-1995-00
Specifications
Dimensions: 6.6"H x 2.75"W x 1.5"D
Weight: .11 lb.
Power Requirements
Alarm LED: 2.8 - 32 VDC, 10 mA max.
Test Coil: 15.5 - 32 VDC, 95 mA max.
Total Current: 105 mA max.
Test Switch: 10 VA @ 32 VDC
Reset Switch: 10 VA @ 32 VDC
Alarm Response Time: 40 seconds max.
Operating Temperature Range: -10°C to 60°C (14°F to 140°F)
Humidity: 95% RH, noncondensing
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - A Division of Pittway

F440-02-00 1 I56-648-03RTC Remote Test Coil Kit for usewith the B404B and B404BT BasesINSTALLATION AND MAINTENANCE INSTRUCTIONSA Division of Pittway 3

Página 2 - TERMINAL

F440-02-00 2 I56-648-03 © System Sensor 1997Three-Year Limited WarrantySystem Sensor warrants its enclosed remote test coil to be free from de-fects i

Comentários a estes Manuais

Sem comentários