PDRP-2001 Series
PRE-ACTION/DELUGE CONTROL PANEL
Instruction Manual
Vista de página 0
1 2 3 4 5 6 ... 147 148

Resumo do Conteúdo

Página 1

E1P/N 53043:E1 ECN 11-162Document 530432/28/2011 Rev:3825 Ohio AvenueSt. Charles, IL 601741-800-SENSOR2Fax: (630) 377-6495PDRP-2001 Series

Página 2 - Fire Alarm System Limitations

10 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 Main Circuit Board 66TB6ZONE6SW1TB4/TB61/62354AAAADummy

Página 3 - FCC Warning

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 100Section 5: Power Supply Calculations5.1 OverviewThis section contains instructions and tables f

Página 4 - Documentation Feedback

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 101Calculating the System Current Draw Power Supply Calculations5.3 Calculating the System Current

Página 5 - Table of Contents

102 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Power Supply Calculations Calculating the System Current DrawTable 5.3 contains three columns fo

Página 6

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 103Calculating the Battery Size Power Supply Calculations5.4 Calculating the Battery SizeUse Table

Página 7

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 104Appendix A: Circuit Mapping and Cross-ZoningA.1 Input-to-Output Circuit Mapping and Cross-Zone

Página 8

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 105Input-to-Output Circuit Mapping and Cross-Zone Operation Circuit Mapping and Cross-ZoningA.1.1

Página 9

106 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Circuit Mapping and Cross-Zoning Input-to-Output Circuit Mapping and Cross-Zone OperationA.1.2

Página 10 - Supervisory*

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 107Input-to-Output Circuit Mapping and Cross-Zone Operation Circuit Mapping and Cross-ZoningExample

Página 11 - FIRE ALARM ANNUNCIATOR

108 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Circuit Mapping and Cross-Zoning Input-to-Output Circuit Mapping and Cross-Zone OperationA.1.3

Página 12 - 1.1 Product Features

109 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix B: FACP Configuration TemplatesThe PDRP-2001 has been provided with preprogrammed templ

Página 13 - 1.2 Specifications

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 11 -+-+JP1JP3SW1JP4TB3TB4TB2ENABLE AC DELAY16 HRDELAYTENSONESCUT FOR240VACGND FLTDISABLEAM-1 ENABL

Página 14

110 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 1: Single Hazard - 3 ZoneB.1 Template 1: Single Hazard -

Página 15

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 111Template 1: Single Hazard - 3 Zone FACP Configuration TemplatesFACP Relay OperationThe following

Página 16 - 1.3 Controls and Indicators

112 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 2: Single Hazard - Cross-Zone With Manual ReleaseB.2 Temp

Página 17 - 1.4 Components

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 113Template 2: Single Hazard - Cross-Zone With Manual Release FACP Configuration TemplatesFACP Rela

Página 18

114 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 3: Dual Hazard - Combined ReleaseB.3 Template 3: Dual Haz

Página 19 - Section 2: Installation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 115Template 3: Dual Hazard - Combined Release FACP Configuration TemplatesFACP Relay OperationThe f

Página 20 - Installation Backbox Mounting

116 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 4: Dual Hazard - Split ReleaseB.4 Template 4: Dual Hazard

Página 21 - Backbox Mounting Installation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 117Template 4: Dual Hazard - Split Release FACP Configuration TemplatesFACP Relay OperationThe foll

Página 22 - 2.2 Operating Power

118 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 5: Single Hazard - 3 Zones and Low PressureB.5 Template 5

Página 23

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 119Template 5: Single Hazard - 3 Zones and Low Pressure FACP Configuration TemplatesFACP Relay Oper

Página 24 - 2.3 Input Circuits

12 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Section 1: Product DescriptionThe PDRP-2001 is a six zone FACP for single and dual hazard deluge

Página 25

120 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 6: Single Hazard - 2 Zones Cross-Zoned With All ActiveB.6

Página 26 - 2.4 Output Circuits

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 121Template 6: Single Hazard - 2 Zones Cross-Zoned With All Active FACP Configuration TemplatesFACP

Página 27 - 2.4.3 Relays - Programmable

122 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011FACP Configuration Templates Template 7: Single Hazard - Dual ZoneB.7 Template 7: Single Hazard

Página 28 - RP2001cULwire.wmf

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 123Template 7: Single Hazard - Dual Zone FACP Configuration TemplatesFACP Relay OperationThe follow

Página 29 - Installation

124 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix C: NFPA Standard-Specific RequirementsThis panel has been designed for use in commercia

Página 30 - B+ B

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 125NFPA Standard-Specific RequirementsThe following figure illustrates an example of Central Statio

Página 31 - Standoffs

126 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011NFPA Standard-Specific Requirements Notes:1. Reference the 411UD Manual for additional informat

Página 32 - 4xtmf.cdr

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 127NFPA 72 Auxiliary Fire Alarm System NFPA Standard-Specific RequirementsC.1 NFPA 72 Auxiliary Fi

Página 33 - 2.7 ANN-BUS Devices

128 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm SystemNFPA 72 Remote Station Pr

Página 34 - 2.7.1 ANN-BUS Wiring

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 129NFPA 72 Auxiliary Fire Alarm System NFPA Standard-Specific RequirementsNFPA 72 Proprietary Prote

Página 35

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 13Specifications Product Description• Indicators Fire Alarm Supervisory Trouble AC Power Alarm

Página 36 - Wiring Configuration

130 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011NFPA Standard-Specific Requirements Central Station/Remote Station Transmitter: Connection to FA

Página 37 - Specifications

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 131Appendix D: FACP with KeltronThe following figure illustrates the connections between the FACP a

Página 38 - Wiring ANN-80 to FACP

132 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix E: Testing & MaintenanceE.1 TestingE.1.1 InspectionOnce installation has been com

Página 39 - ANN-BUS Devices Installation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 133Maintenance Testing & MaintenanceTest i3 Series detectors as follows:Test Sw itch1. An openi

Página 40 - PRN-6F Printer Installation

134 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix F: Wire RequirementsConnecting external system accessories to the main circuits must be

Página 41

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 135NAC Wiring Wire RequirementsF.1 NAC WiringThe following table lists NAC wiring requirements for

Página 42 - ANN-I/O Board Layout

136 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix G: Compatible DevicesG.1 Compatible Two-Wire Smoke Detectors (UL Listed)Canadian Appli

Página 43 - ANN-I/O Module LED Wiring

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 137Maximum Number of Detectors per Zone Compatible DevicesG.2 Maximum Number of Detectors per Zone

Página 44 - Mounting/Installation

138 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Compatible Devices Four-Wire Smoke Detectors/Devices (UL Listed)G.3 Four-Wire Smoke Detectors/D

Página 45 - 2.7.7 ANN-RLY Relay Module

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 139Notification Appliances (UL Listed) Compatible DevicesG.4 Notification Appliances (UL Listed)Co

Página 46

14 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Product Description SpecificationsBattery (sealed lead acid only) - J12Maximum Charging Circuit -

Página 47 - Section 3: Programming

140 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Compatible Devices Notification Appliances For Canadian ApplicationsG.4.2 System Sensor SpectrA

Página 48 - 3.2 Initial Power-up

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 141Door Holders (UL Listed) Compatible DevicesG.7 Door Holders (UL Listed) G.8 Relays (UL Listed)

Página 49 - Programming Screen #1

142 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011IndexNumerics2nd-Shot Water Switch 53AAC Loss Delay 67, 69AC power 22rating 13requirements 100ac

Página 50 - 3.5 Master Programming Level

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 143Index D–Lcurrent requirements for system 101, 102DDate setting 71Daylight Savings Time 71, 98Des

Página 51 - 3.5.2 Input Zones

144 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011M–P IndexMMain 10maintenance 24piezo pulse rate 16Maintenance Alert 91Maintenance Program Level

Página 52 - Zone Type Screen #1

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 145Index R–VRRead Status 47, 93ANN-BUS 99Configuration 94Cross Input Zones 96exiting 48history 98In

Página 53

146 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011W–Z IndexWWalktest 80, 92audible 80Maintenance Level 84operation 92silent 80Waterflow Delay time

Página 54 - Output Zone Screen#2

Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. Subject to the limitations set forth herein,Manufacturer warrants that th

Página 55 - *****************

3825 Ohio AvenueSt. Charles, IL 60174-54651-800-SENSOR2Fax: (630) 377-6495

Página 56 - INPUT ZONE #

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 15Specifications Product DescriptionSpecial Application Resettable or Nonresettable Power - TB9Oper

Página 57 - 3.5.3 Output Circuits

16 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Product Description Controls and Indicators1.3 Controls and IndicatorsLCD Display The FACP us

Página 58 - Edit Output # Type Screen

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 17Components Product Description1.4 ComponentsMain Circuit BoardThe main circuit board contains th

Página 59

18 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Product Description Optional Modules and AccessoriesTR-CE Trim-ringA trim-ring TR-CE (red) is ava

Página 60 - Silenceable Screen #2

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 19Section 2: InstallationThe cabinet can be surface mounted or semi-flush mounted. The door is rem

Página 61 - Silence Inhibited

2 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Fire Alarm System LimitationsWhile a fire alarm system may lower insurance rates, it is not a subs

Página 62 - Coding Screen #4

20 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Backbox MountingTB6SW1mounting studsmounting slotsmounting tabsmounting holesgroundi

Página 63

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 21Backbox Mounting Installation9050UDencl.cdrFigure 2.2 Cabinet DimensionsHinge Slot for optional

Página 64 - 3.5.4 Cross Input Zones

22 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Operating Power 2.2 Operating PowerPrimary Power Source (AC) and Eart

Página 65 - 3.5.5 On-Board Relays

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 23Operating Power Installationprovided with overcurrent protection and may not contain any power di

Página 66 - 3.5.6 System Setup

24 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Input Circuits2.3 Input CircuitsThe PDRP-2001 has six programmable IDCs (Initiating

Página 67

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 25Input Circuits InstallationCombination Waterflow/Supervisory ZoneA combination Waterflow/Supervis

Página 68 -  Waterflow Delay

26 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Output Circuits2.4 Output Circuits2.4.1 Outputs/Notification Appliance/Releasing C

Página 69 - AC Loss Delay Screen #1

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 27Output Circuits Installation2.4.2 Special Application DC Power Output ConnectionsSpecial Applica

Página 70 - Time-Date

28 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Power-limited Wiring Requirements2.5 Power-limited Wiring RequirementsPower-limited

Página 71 - Daylight Savings Screen #2

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 29Installation of Optional Modules Installation2.6 Installation of Optional Modules2.6.1 CAC-5X C

Página 72 - SYSTEM SETUP

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 3Installation PrecautionsAdherence to the following will aid in problem-free installation with long

Página 73 - 3.5.7 ANN-BUS

30 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Installation of Optional ModulesWiring NACs and IDCs for Class AWire the Style Z (Cl

Página 74 - ANN-BUS Modules

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 31Installation of Optional Modules Installation2.6.2 4XTMF Municipal Box Transmitter Option Module

Página 75 - ANN-S/PG Options

32 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation Installation of Optional ModulesMaximum Coil Resistance: 14.6 ohmsMaximum allowable

Página 76 - ANN-I/O LED Zone Assignments

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 33ANN-BUS Devices Installation2.6.3 ANN-SEC Option CardThe ANN-SEC option card allows for a second

Página 77 - ANN-80 Options

34 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS Devices2.7.1 ANN-BUS WiringThis section contains information on calculating

Página 78 - 3=RELAY 3 IN ZONE 3

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 35ANN-BUS Devices InstallationException: When using the ANN-RLY module, the installer must ensure

Página 79 - 3.5.8 History

36 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS DevicesWiring ConfigurationFigure 2.16 illustrates the wiring between the FA

Página 80 - 3.5.9 Walktest

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 37ANN-BUS Devices Installation2.7.2 ANN-BUS Device AddressingEach ANN-BUS device requires a unique

Página 81 - 3.5.11 Password Change

38 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS DevicesThe ANN-80 cover must be attached to the annunciator backplate before

Página 82

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 39ANN-BUS Devices Installation6. If appropriate, connect the power wiring going to the next device

Página 83 - 3.6.2 History

4 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Software DownloadsIn order to supply the latest features and functionality in fire alarm and life

Página 84 - 3.6.3 Walktest

40 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS Devices2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.193. U

Página 85 - 3.6.4 Time-Date

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 41ANN-BUS Devices InstallationSetting Printer OptionsRefer to the documentation supplied with the

Página 86 - 4.1 Panel Control Buttons

42 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS DevicesANN-I/O Board LayoutFigure 2.20 illustrates the ANN-I/O board showing

Página 87 - 4.3 Normal Operation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 43ANN-BUS Devices InstallationANN-I/O Connection to FACPThe ANN-I/O connects to the FACP via the AN

Página 88 - 4.4 Trouble Operation

44 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS DevicesThe LEDs are wired as illustrated in Figure 2.22. Note that the illu

Página 89 - 4.5 Alarm Operation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 45ANN-BUS Devices InstallationANN-LED Board Layout and Connection to FACPFigure 2.23 illustrates th

Página 90 - 4.7 Disable/Enable Operation

46 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Installation ANN-BUS DevicesMounting/InstallationThe ANN-RLY relay module can be mounted inside t

Página 91 - 4.11 Coded NAC Operation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 47Section 3: Programming3.1 User ProgrammingThe FACP is completely field programmable using the pa

Página 92 - 4.14 Walktest

48 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Initial Power-upPressing 1, while this screen is being displayed, will cause the cont

Página 93 - 4.15 Read Status

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 49Programming and Passwords Programming3.4 Programming and PasswordsThere are two factory set prog

Página 94 - 4.15.2 Input Zones

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 5Table of Contents Section 1: Product Description ...

Página 95 - 4.15.3 Output Circuits

50 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming Level3.5 Master Programming LevelWhen the Master Program Level pa

Página 96 - 4.15.5 On-Board Relays

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 51Master Programming Level Programming3.5.1 FACP CONFIG (Application Templates)For a detailed desc

Página 97 - 4.15.7 Timers

52 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelTo change the programming for the displayed zone, press the k

Página 98 - 4.15.10 Print

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 53Master Programming Level ProgrammingPressing the down arrow key displays additional zone types as

Página 99 - 4.15.11 ANN-BUS

54 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelOutput Circuit MapOutput Mapping (per input zone) allows the

Página 100 - 5.1 Overview

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 55Master Programming Level ProgrammingAdjective/NounThe Adjective/Noun selection allows the program

Página 101 - Current Draw

56 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelPressing 2 while viewing the Adjective/Noun Screen will cause

Página 102

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 57Master Programming Level ProgrammingA maximum of 20 characters (including spaces) can be entered.

Página 103

58 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelThe Output Circuits can be configured independently by pressi

Página 104 - Operation

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 59Master Programming Level ProgrammingPressing the down arrow key while viewing the Edit Output Typ

Página 105

Table of Contents6 PDRP-2001 Series Manual — P/N 53043:E1 2/28/20113.4: Programming and Passwords...

Página 106 - Activation

60 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelAn NAC can be used to signal the stages of a release operatio

Página 107

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 61Master Programming Level ProgrammingAuto SilenceThe Auto Silence feature, when enabled, automatic

Página 108 - Release Circuits

62 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming Levelwill cause a screen to be displayed with the options 1=No Sil

Página 109

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 63Master Programming Level ProgrammingThe programmer can select the notification appliance output c

Página 110

64 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming Level3.5.4 Cross Input ZonesAn application may require that two o

Página 111

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 65Master Programming Level ProgrammingIn this example, since the cross-zoning for Release Circuit 1

Página 112

66 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelWhile viewing the selected screen, press the number correspon

Página 113

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 67Master Programming Level ProgrammingPressing 3 for System Setup, while viewing Programming Screen

Página 114

68 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelSoak 1 or Soak 2The factory default setting for Soak Time is

Página 115

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 69Master Programming Level ProgrammingAC Loss DelayThe reporting of a loss of AC power can be dela

Página 116

Table of ContentsPDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 74.12: Release Stages...

Página 117

70 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelPressing 2 while viewing the Select Banner Screen will displa

Página 118

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 71Master Programming Level ProgrammingA flashing cursor is located toward the top left of the displ

Página 119

72 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelPressing 1 while viewing Daylight Savings Screen #1 will caus

Página 120 - All Active

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 73Master Programming Level Programming• The installer must write in the Date of Final Assembly on t

Página 121

74 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelANN-BUS ModulesIf an ANN-BUS module is installed, press 2 whi

Página 122

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 75Master Programming Level ProgrammingAuto-ConfigureThe ANN-BUS Auto-Configure features allows the

Página 123

76 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelIf the Parallel Port option is selected, the user has the abi

Página 124

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 77Master Programming Level ProgrammingANN-80 OptionsPressing 2 while ANN-BUS screen #2 will display

Página 125 - 1 2 3 4 5 6 7

78 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming LevelANN-RLY OptionsPressing 1 for ANN-RLY Options while viewing A

Página 126

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 79Master Programming Level Programming3.5.8 HistoryThe History option allows an authorized user to

Página 127

Table of Contents8 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Appendix F: Wire Requirements ...

Página 128

80 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Master Programming Level3.5.9 WalktestWalktest allows an individual to test the fire

Página 129

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 81Master Programming Level Programming3.5.10 Clear ProgramPressing 1 while viewing Programming Scr

Página 130

82 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Maintenance Programming Level3.6 Maintenance Programming LevelTo access Maintenance

Página 131 - Appendix D: FACP with Keltron

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 83Maintenance Programming Level Programming3.6.1 Input Zones - Enable/DisableThe Input Zones optio

Página 132 - E.1 Testing

84 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Programming Maintenance Programming LevelTo view all the events which have occurred in the contro

Página 133 - E.2 Maintenance

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 85Maintenance Programming Level Programming3.6.4 Time-DateTo program the time and date into the co

Página 134 - Appendix F: Wire Requirements

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 86Section 4: Operating InstructionsFactory programmed Templates have been provided to facilitate th

Página 135 - F.1 NAC Wiring

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 87Indicators Operating Instructions4.2 IndicatorsThe six indicators, which are located on the fron

Página 136

88 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Trouble Operationi3 smoke detectors will be polled for maintenance and fr

Página 137

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 89Alarm Operation Operating Instructions• Fourth line in display: Time; the current time in this e

Página 138

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 9It is imperative that the installer understand the requirements of the Authority Having Jurisdicti

Página 139 - G.4.1 System Sensor - 24VDC

90 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Supervisory Operation• Second line in display: <ADJ>; refers to the

Página 140 - G.6 Releasing Applications

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 91Waterflow Circuits Operation Operating InstructionsNote that disabled Releasing Circuits are trea

Página 141 - G.8 Relays (UL Listed)

92 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Release Stages• Synchronized output for System Sensor, Wheelock, Gentex, F

Página 142 - Numerics

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 93Read Status Operating Instructionswalktest information in a file which can be viewed at the panel

Página 143 - Index D–L

94 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Read StatusThe following screens will be displayed:4.15.1 FACP Configurat

Página 144 - M–P Index

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 95Read Status Operating InstructionsThe operator selects the zone which is to be viewed by pressing

Página 145 - Index R–V

96 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Read Status4.15.4 Cross Input ZonesPressing 1 while viewing Read Status S

Página 146 - W–Z Index

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 97Read Status Operating Instructions4.15.6 System SettingsPressing 3 while viewing Read Status Scr

Página 147 - Warn-HL-08-2009.fm

98 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011Operating Instructions Read Status4.15.8 Daylight SavingsPressing 2 while Read Status Screen #3

Página 148 -

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011 99Read Status Operating InstructionsPressing 1 allows the user to print the History file which will