128 PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011
NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the PDRP-2001 main circuit board to supervise placement of the 4XTMF
module.
2. Refer to “4XTMF Transmitter Module Installation” on page 31 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
+ -
Polarity Shown is
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
Power-limited
Figure C.3 Remote Station Connection Using 4XTM Module
+
-
(Dummy load with a 4.7K ¼ watt resistor
when no connection is made)